What is the approximate maximum rated secondary current of a 500KVA 25KV Delta to 347/600V Wye transformer?

  • a) 481 A
  • b) 833 A
  • c) 1019 A
  • d) 1440 A

A unit substation transformer has a rated secondary current of 2100A without a fan kit. It has an option to add a fan kit. What would be the rating of the secondary current if a fan kit was added?

  • a) 2800A
  • b) 2900A
  • c) 3000A
  • d) 3100A

What is the approximate maximum rated secondary current of a 750KVA 25KV Delta to 347/600V Wye transformer?

  • a) 2161 A
  • b) 1528 A
  • c) 1250 A
  • d) 722 A

A unit substation transformer has a rated secondary current of 1500A without a fan kit. It has an option to add a fan kit. What would be the rating of the secondary current if a fan kit was added.

  • a) 1700A
  • b) 1800A
  • c) 1900A
  • d) 2000A

What is the approximate maximum rated secondary current of a 1200KVA 25KV Delta to 347/600V Wye transformer?

  • a) 1165 A
  • b) 3458 A
  • c) 2445 A
  • d) 2000 A

Let's say you have a standard 400A 120/208V branch panel, and it’s fed from a 400A 3P breaker 30m away.

 Referring to Table 2 from the CEC (below) which size of wire should be selected for the feeder for a single run, and which size of wire from the table below should be selected for the feeder for a parallel run?

  • a) Size 500 for the single run feeder, and size 000 (3/0) for the parallel run
  • b) Size 600 for the single run feeder, and size 000 (3/0) for the parallel run
  • c) Size 400 for the single run feeder, and size 000 (2/0) for the parallel run
  • d) Size 500 for the single run feeder, and size 000 (2/0) for the parallel run

At what distance would you start considering voltage drop for a 3ph 347/600V panel feeder (copper in EMT)?

  • a) 100ft (30.5m)
  • b) 300ft (91.5m)
  • c) 600ft (183m)
  • d) 1000ft (304m)

At what distance would you start considering voltage drop for a 3ph 120/208V panel feeder (copper in EMT)?

  • a) 75ft (23m)
  • b) 125ft (38m)
  • c) 200ft (61m)
  • d) 350ft (107m)